Kelman TRANSPORT X* portable DGA (Dissolved Gas Analysis) and moisture in oil

Product Overview


Accurate knowledge of the condition of transformers is essential for all electrical networks. This information allows valuable asset capabilities to be maximised and expensive failures to be avoided.

Dissolved Gas Analysis (DGA) is an established technique and is recognised as the most important test in monitoring power transformers. It is now being successfully extended to other oil filled equipment such as tap changers and circuit breakers.

The TRANSPORT X is a compact, portable DGA system which is designed to analyse oil samples in the field and obtain not only gas level readings but also deliver diagnostics based on standard rules.

The TRANSPORT X unit has been designed to be very rugged and user friendly with an emphasis placed on easy field operation. The unit is used by over 200 companies and utilities and has sold in excess of 1000 units worldwide.


Features & Benefits

The TRANSPORT X test uses state of the art infrared measurement technology to give accurate, reliable results in a matter of minutes. The TRANSPORT X product represents an invaluable tool for Asset Management and will increase the power of any DGA program.

Extensive field and laboratory use worldwide has proven that the TRANSPORT X test gives highly reliable results and that it is genuinely suitable for field conditions.

The TRANSPORT X equipment minimises the risk of carry-over between tests. With the ability to go from high gassed samples (such as tap changers) to subsequent low gassed samples (such as main tanks) with no contamination of results the user can confidently test all types of oil filled equipment.

Internal diagnostic software helps to translate ppm data into valuable information by employing standard DGA interpretation rules e.g. Duval’s triangle, key gas analysis etc.


Accurate & Sensitive
The TRANSPORT X unit has a wide detection range with excellent accuracy for all seven fault gases.

Moisture Analysis
The unit measures water content in oil. The water concentration can be expressed as parts per million or relative saturation.

Simple
Easy step-by-step operation. No extensive calibration, set-up or interpretation of results required.

Fast
On-site results in less than thirty minutes.

No Consumables
The TRANSPORT X unit requires no calibration or carrier gases.

Portable & Rugged
11kg (24lbs) in a rugged convenient carry case.

DGA Diagnostics
Includes DGA diagnostic algorithms - Rogers’ Ratios, Duval’s Triangle, Japanese ETRA and IEEE® Key gas. Also includes user settable “Caution and Warning” thresholds on all gases.

Test Gas Samples
Ability to test gas samples taken from Buchholz Relays.